Air-cooled technologies : Recent key facts
WORLD'S LARGEST TURBOGENERATOR IN OPERATION:
1980-1990: Constant air cooled generator technology evolution from 100 to 200 MW
1990-1995 : Development and market introduction of 250 MW class air-cooled generator.
1995-2000 : Development and tests of 300-400 MW class air-cooled generator, to anticipate the large GT's and combined cycle development
TOPAIR 25 Generator : MAIN FEATURES
Basic
design based on experience and proven technologies
Stator
insulation : Single bar VPI (Micadur / Class F +(155°C)
Stator
cooling : Indirect / Multichamber cooling
Rotor
cooling : Direct / Axial with subslots
Larger
output achieved by sizes increase : (D+7% L+17%)
Linear
current density (up to +20%) tanks to the following features
Reverse
cooling (6 air coolers just after fans : 17K enefits)
External
air by-pass and air mixer at cooler outlet
Rotor air
inlet guide vanes
TOPAIR 25 type :
Rated output : 400 MVA
Power factor : 0,85
Active power : 340 MW
Voltage : 21 kV
Cooling : AIR
Excitation : Static
Operation : IEC Class B
MAIN DATA:
TYPE TEST: